Understanding Code Requirements

for an HVAC Service Receptacle

by: Matt Buecker


 

WP GFCI service receptacle

The National Electrical Code, Section 210.63 states that a power receptacle is required for service technicians to use when repairing a hvac unit. A long-time building department favorite, it is closely regulated and has become a design standard for electrical engineers. Listed below is section 210.63 in the NEC 2008:



210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet

A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and with 7.5m (25 ft) of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means.


Weatherproof GFCI receptacle

There are a few important points to mention here. First off, a hvac equipment outlet is required no matter where an hvac unit is located. This means that whether the unit is mounted on the floor, in a closet, in a ceiling, is exterior pad mounted or roof mounted, this code is required. Quite often this is overlooked for air-handling units located in ceiling space but a service receptacle is required within the ceiling for this unit.

The next thing of importance is that when a service receptacle occurs in an exterior location, it must be GFCI protected per 210.8(B) and have a weatherproof enclosure per 406.8 (now 406.9 in NEC 2011).

Third, this applies to all types of hvac units except for evaporative coolers. This means that in a situation where a warehouse has rooftop exhaust fans and no cooling equipment, it must have a service receptacle. But for a residential dwelling unit in the Southwest US that has an evaporative cooling unit (in window), a service receptacle is not required.

Finally, the last sentence in this code section is significant. It is becoming more common for rooftop "package" units to have the service receptacle mounted into the frame as opposed to being mounted on the roof surface. This receptacle must be connected to a branch circuit that is not serving the rooftop unit. This means that the service receptacle cannot be powered by one of the legs to the rooftop unit. The logic is that if the unit is being serviced and power to it is shut-off, the service receptacle must remain energized. Also notable, the Code makes no mention about the service receptacle being a dedicated outlet. It is common design practice to group exterior and roof receptacles on a circuit together, as long as the load does not exceed 20 amps.

One last note: This section remains unchanged in the NEC 2011.



For more information about changes/additions to NEC 2011, click here.

Our Network:
Electrical Design
AutoCad Basics
Revit Basics


Click Here
to Download
Top 10 Changes to
NEC  2011

Free!


DMCA.com
affiliate_link